HVAC Zone Control Systems Model ZCV6 6 Zone HVAC Zone Control Unit With RS232/RS485 Serial Communications INS
DCN 141-01068 -01 2/06/06 10 COMMUNICATIONS Communications Setup and Wiring RS232 Communications When the RS232 communications mode is selected,
DCN 141-01068 -01 2/06/06 11 RS485 Communications When the RS485 communications mode is selected, the ZCV6 COM port is a 2 wire (D+ and D –) plus g
DCN 141-01068 -01 2/06/06 12 Termination Resistor On multi-drop network wiring, the last device on the network is typically installed with an “end o
DCN 141-01068 -01 2/06/06 13 HVAC SYSTEM WIRING Electrically, the ZCV6 Control Unit looks like a standard thermostat to your HVAC system. All conn
DCN 141-01068 -01 2/06/06 14 SYSTEM CHECKOUT It is strongly recommended that you hook-up and run a simple bench test before installing this contro
DCN 141-01068 -01 2/06/06 15 HVAC SYSTEM QUICK TEST In the event that you have difficulty with the ZCV6 controlling the HVAC system, you can perfor
DCN 141-01068 -01 2/06/06 16 ZCV6 6 ZONE HVAC CONTROL UNIT Wiring Diagram Zone Dampers Normally Open RD Series 2 Wir
DCN 141-01068 -01 2/06/06 2
DCN 141-01068 -01 2/06/06 3 OPERATION The ZCV6 HVAC Zone Control Unit allows a single HVAC mechanical system to be divided into six fully independ
DCN 141-01068 -01 2/06/06 4 Outside Temperature Operation The ZCV6 can use and display outside temperature information from a sensor attached to th
DCN 141-01068 -01 2/06/06 5 HVAC CONTROL OPERATION AND SETUP STANDARD HVAC SYSTEMS Heat and Cool Mode Operation. In the HEAT mode, the heati
DCN 141-01068 -01 2/06/06 6 HEAT PUMP HVAC SYSTEMS HEAT PUMP SYSTEM OPERATION Heat Pump HVAC Systems use the system’s compressor for both heating
DCN 141-01068 -01 2/06/06 7 NETWORK OPERATION The ZCV6 HVAC controller has the option for either RS-232 or RS-485 serial communications. The ser
DCN 141-01068 -01 2/06/06 8 INSTALLATION LOCATION AND MOUNTING Install the Control Unit in a protected, convenient, INDOOR location near the HVAC
DCN 141-01068 -01 2/06/06 9 Wiring To The Zone Dampers Wire specification: 2 conductor for RD or 3 conductor for RDM series dampers, standard 18